| WISE-5800 |
|
|
|
| |
Introduction |
WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development.
WISE-5800 supports an I/O expansion bus to implement various I/O functions such as D/I, D/O, A/D and D/A according to the XW-Board. In addition, it also support ICP DAS I-7000 / M-7000 remote I/O modules and Modbus RTU slave devices. Based on the variety I/O module of I-7000 / M-7000 and the connection ability with Modbus RTU slave devices, WISE-5800 can provide user more flexibility in application field.
WISE-5800 supports Modbus TCP/RTU protocol to make seamless integration with SCADA software available. It include all advantages which WISE series controllers can provide. In addition, WISE-5800 provide data logger function with microSD card, it can record I/O channel value by event trigger or regular time period. The data files can be sent back by Email or FTP. All setting can be completed through browser.
In addition to merits inherited from the existing WISE series, WISE-5800 even provides more supports in I/O functions. It allows to connecting with a wide range of XW-Boards, I-7000 / M-7000 Remote I/O modules and Modbus RTU slave devices that enables users to freely choose the most suitable I/O modules. With the microSD card, it provides Data Logger function to real-time record the I/O data of the controller and send the data files by FTP or Email at a scheduled time to the control center for further administration management or data analysis.

|
|
| |
|
| |
Features |
‧Built-in Web Server for IF-THEN-ELSE rule setting
‧Built-in IF-THEN-ELSE rule enigne for logic operation
‧Support IO, Counter, Timer, Schedule, Email, Recipe operations
‧No more programming. Just click and get done!
‧Data logger and data files send back function supported
‧Modbus TCP/RTU Protocol for SCADA Software Seamless Integration
‧10/100 Base-TX Ethernet
‧Support XW-Board
‧Support I-7000 Remote I/O Modules(Up to 16)
‧Support M-7000 / Modbus RTU Slave Devices(Up to 10)
‧SNTP Time Synchronization Supported
|
|
| |
|
| |
Support I/O Module List |
| I/O Type |
Functions |
Modules |
| I-7000 Remote I/O Module |
AI/AO |
Voltage & Current |
I-7012, I-7012D, I-7012F, I-7012FD
I-7017, I-7017F, I-7017R, I-7017C, I-7017FC, I-7017RC, I-7017R-A5, I-7017Z |
| Thermocouple |
I-7011, I-7011D, I-7011P, I-7011PD
I-7018, I-7018BL, I-7018P, I-7018R, I-7018Z
I-7019R |
| RTD |
I-7013, I-7013D
I-7015, I-7015P
I-7033, I-7033D |
| Thermistor |
I-7005 |
| Transmitter |
I-7014D |
| Analog Output |
I-7021, I-7021P
I-7022
I-7024, I-7024R |
| DI/DO |
DC Digital Input |
I-7041, I-7041D, I-7041P, I-7041PD
I-7051, I-7051D
I-7052, I-7052D
I-7053_FG, I-7053D_FG |
| AC Digital Input |
I-7058, I-7058D
I-7059, I-7059D |
| DC Digital Output |
I-7042, I-7042D
I-7043, I-7043D
I-7045, I-7045D, I-7045-NPN, I-7045D-NPN |
| DC Digital Input & Output |
I-7044, I-7044D
I-7050, I-7050D, I-7050A, I-7050AD
I-7055, I-7055D, I-7055-NPN, I-7055D-NPN |
| Relay Output |
Power Relay Output |
I-7060, I-7060D
I-7061, I-7061D
I-7063, I-7063D
I-7065, I-7065D
I-7067, I-7067D |
| Solid State Relay Output |
I-7063A, I-7063AD, I-7063B, I-7063BD
I-7065A, I-7065AD, I-7065B, I-7065BD |
| Photomos Relay Output |
I-7066, I-7066D |
| Others |
Counter/Frequency |
I-7080, I-7080D, I-7080B, I-7080BD
I-7088 |
| DL Series |
Temperature and Humidity |
DL-100T485 |
| XW-Board |
DI/DO |
XW107, XW110 |
| DI/DO/AI/AO |
XW304, XW310, *XW310C |
| M-7000 / Modbus RTU Slave Module |
Coil Output / Discrete Input / Input Register / Holding Register |
|
| (* = Available Soon) |
|
|
| |
|
| |
Applications |
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc. |
|
| |
|
| |
Hardware Specifications |
| CPU Module |
| CPU |
16-bit CPU |
| SRAM |
768 KB |
| Flash |
512 KB |
| EEPROM |
16 KB |
| NVRAM |
31 Bytes |
| microSD Expansion |
Yes, can support 1 or 2 GB microSD |
| RTC (Real Time Clock) |
RTC Provide seconds, minutes, hours, date of week/month; month and year |
| Watchdog Timers |
Yes (0.8 second) |
| Communication Ports |
| Ethernet |
RJ-45 x 1, 10/100 Base-TX (Auto-negotiating, Auto MDI/MDI-X, LED indicators) |
| COM 1 |
RS-232 (TxD, RxD, RTS, CTS, GND), non-isolated, Speed: 115200 bps max. |
| COM 2 |
RS-485 (D2+, D2-), self-tuner ASIC inside, non-isolated, Speed : 115200 bps max. |
| LED Indicators |
| System LED |
Yes (Red) |
| Ethernet Link LED |
Yes (Green : Ethernet link detected, Flashing Green : Ethernet packet received) |
| LED Display |
- |
| Hardware Expansion |
| I/O Expansion Bus |
Yes |
| Mechanical |
| Dimensions (W x H x D) |
91 mm x 123 mm x 52 mm |
| Installation |
DIN-Rail |
| Environment |
| Operating Temperature |
-25 ~ +75 °C |
| Storage Temperature |
-30 ~ +80 °C |
| Ambient Relative Humidity |
10 ~ 90% RH (non-condensing) |
| Power |
| Protection |
Power reverse polarity protection |
| Frame Ground |
Yes (for ESD Protection) |
| Input Range |
+12 ~ +48 VDC |
| Redundant Power Input |
Yes |
| Power Consumption |
2.0 W |
|
|
| |
|
| |
Software Specifications |
| Functions |
| Rule Configuration Website |
Access Web server on WISE controllers to edit and upload logic rules through web browser.
|
| 36 IF-THEN-ELSE Logic Rules |
3 IF conditions with AND or OR operators
3 THEN actions and 3 ELSE actions
|
| 48 Internal Registers |
Hold temporary variables and read/write data via Modbus/TCP address.
|
| 12 Timers |
Delay / Timing functions.
|
| 12 Schedules |
Setup prescheduled routine tasks.
|
| 12 Emails |
Send Email messages to pre-set Email receivers.
|
| 12 CGI Commands |
Send pre-set CGI commands.
|
| 12 Recipes |
Set up THEN/ELSE action groups.
|
| Data Logger |
Set up the Data Logger configuration, include the data record format, and data file sending operation.
|
| Modbus TCP/RTU Protocol |
Real time control and monitoring I/O channels and system status of controllers via SCADA software.
|
| IF Conditions |
| DI Channel |
ON、OFF、ON to OFF、OFF to ON、Change |
| AI Channel |
=、>、<、>=、<=(value) |
| Internal Register |
| DI Counter |
=、>、<、>=、<=(value)、Change |
| Timer |
Timeout、Not Timeout |
| Schedule |
In Range、Out of Range |
| Rule Status |
Enable、Disable |
| THEN / ELSE Actions |
| DO Channel |
ON、OFF、Pulse Output (Just for XW-Board) |
| AO Channel |
Change the value |
| Internal Register |
| DI Counter |
Reset |
| Timer |
Start、Reset |
| Schedule |
Enable、Disable |
| Email |
Send |
| CGI Commands |
| Recipe |
Execute |
| Data Logger |
Start、Stop、One-Time Log |
| Rule Status |
Enable、Disable |
|
|
| |
|
| |
Ordering Information |
| WISE-5800 |
| User-defined I/O & Data Logger Module |
|
|
| |
|
| |
Accessories |
| NS-205 CR |
Unmanaged 5-Port Industrial Ethernet Switch (RoHS) |
| MDR-20-24 CR |
24V/1A, 24 W Power Supply with DIN-Rail Mounting (RoHS) |
| DIN-KA52F CR |
24V/1.04A, 25 W Power Supply with DIN-Rail Mounting (RoHS) |
| 3LMSD-2000 CR |
2 GB microSD card (RoHS) |
|
|
| |
| |
back |