WISE-5800

User-defined I/O & Data Logger Module for Modbus RTU or DCON Devices

Introduction

WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development.

WISE-5800 supports an I/O expansion bus to implement various I/O functions such as D/I, D/O, A/D and D/A according to the XW-Board. In addition, it also support ICP DAS I-7000 / M-7000 remote I/O modules and Modbus RTU slave devices. Based on the variety I/O module of I-7000 / M-7000 and the connection ability with Modbus RTU slave devices, WISE-5800 can provide user more flexibility in application field.

WISE-5800 supports Modbus TCP/RTU protocol to make seamless integration with SCADA software available. It include all advantages which WISE series controllers can provide. In addition, WISE-5800 provide data logger function with microSD card, it can record I/O channel value by event trigger or regular time period. The data files can be sent back by Email or FTP. All setting can be completed through browser.

In addition to merits inherited from the existing WISE series, WISE-5800 even provides more supports in I/O functions. It allows to connecting with a wide range of XW-Boards, I-7000 / M-7000 Remote I/O modules and Modbus RTU slave devices that enables users to freely choose the most suitable I/O modules. With the microSD card, it provides Data Logger function to real-time record the I/O data of the controller and send the data files by FTP or Email at a scheduled time to the control center for further administration management or data analysis.

Features

  • Built-in Web Server for IF-THEN-ELSE rule setting
  • Built-in IF-THEN-ELSE rule enigne for logic operation
  • No more programming. Just click and get done!
  • Support IO, Counter, Timer, Schedule, Email, Recipe operations
  • Data logger and data files send back function supported
  • Modbus TCP/RTU Protocol for SCADA Software Seamless Integration
  • Support XW-Board
  • Support I-7000 Remote I/O Modules (Up to 16)
  • Support Modbus RTU Slave Devices (Up to 10)
  • SNTP Time Synchronization Supported

Applications

Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.

Hardware Specifications

System
CPU 16-bit CPU
SRAM 768 KB
Flash Memory 512 KB
EEPROM 16 KB
NVRAM 31 Bytes
microSD Expansion Support 1G/2G/4G/8G/16G/32G microSD card
RTC (Real Time Clock) Provide second, minute, hour, date of week, month and year
Watchdog Yes
Communication
Ethernet RJ-45 x 1, 10/100 Base-TX (Auto-negotiating, Auto MDI/MDI-X)
COM 1 RS-232 (TxD, RxD, RTS, CTS, GND), non-isolated, Speed: 115200 bps max.
COM 2 RS-485 (D2+, D2-), self-tuner ASIC inside, non-isolated, Speed : 115200 bps max.
LED Indicators
System LED L1 (Flash Red: System is in normal status)
L2 (Green: The microSD card is in normal status and the connection to WISE is OK (for firmware v2.5.5 or later version only))
Ethernet Link LED Yes (Green: Ethernet link detected, Flashing Green: Ethernet packet received)
Hardware Expansion
I/O Expansion Bus Yes
Power Requirements
Protection Power Reverse Polarity Protection
Frame Ground Yes (for ESD Protection)
Input Range +12 ~ +48 VDC
Redundant Power Input Yes
Power Consumption 2.0 W
Mechanical
Dimensions (W x H x D) 91 mm x 123 mm x 52 mm
Installation DIN-Rail
Environment
Operating Temperature -25 °C to +75 °C
Storage Temperature -30 °C to +80 °C
Ambient Relative Humidity 10 to 90% RH, non-condensing

Software Specifications

Functions
Rule Configuration Website Access Web server on WISE controllers to edit and upload logic rules through web browser.
36 IF-THEN-ELSE Logic Rules 3 IF conditions with AND or OR operators
3 THEN actions and 3 ELSE actions
48 Internal Registers Hold temporary variables and read/write data via Modbus/TCP address.
12 Timers Delay / Timing functions.
12 Schedules Setup prescheduled routine tasks.
12 Emails Send Email messages to pre-set Email receivers.
12 CGI Commands Send pre-set CGI commands.
12 Recipes Set up THEN/ELSE action groups.
Data Logger Set up the Data Logger configuration, include the data record format, and data file sending operation.
Modbus TCP/RTU Protocol Real time control and monitoring I/O channels and system status of controllers via SCADA software.
IF Conditions
DI Channel ON, OFF, ON to OFF, OFF to ON, Change
AI Channel =, >, <, ≥, ≤ (value)
Internal Register
DI Counter =, >, <, ≥, ≤ (value), Change
Timer Timeout, Not Timeout
Schedule In Range, Out of Range
Rule Status Enable, Disable
THEN / ELSE Actions
DO Channel ON, OFF, Pulse Output (apply to XW-Board only)
AO Channel Change the value
Internal Register
DI Counter Reset
Timer Start, Reset
Schedule Enable, Disable
Email Send
CGI Commands
Recipe Execute
Data Logger Start, Stop, One-Time Log
Rule Status Enable, Disable

Support I/O Module List

※ If the module name is marked in gray, it means that has been phase out.

searchSearch
Model:
I/O Type:
Functions:

I/O Type Functions Modules

Ordering Information

  • WISE-5800 CR
  • User-defined I/O & Data Logger Module for Modbus RTU or DCON Devices

Accessories