WISE-7115

7-channel RTD Input with 3-wire RTD lead resistance elimination PoE Module

Introduction

WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development.

WISE-7115 follows IEEE 802.3af-compliant (classification, Class 1) Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs (Category 5 Ethernet cable). This feature provides greater flexibility and higher efficiency therefore simplifying systems design, saving space, reducing cables and eliminating the requirement for dedicated electrical outlets. Meanwhile, in case under a non-PoE environment, WISE-7115 will still be able to receive power from auxiliary power sources like AC adapters or battery, etc.

This module WISE-7115 supports Modbus/TCP protocol to make seamless integration with SCADA software available. It features 16-bit, 7-channel RTD inputs. Each channel is allowed to configure an individual range that supports 3-wire RTD lead resistance elimination and open wire detection for RTD measurement.

Features

  • Built-in Web Server for IF-THEN-ELSE rule setting
  • Built-in IF-THEN-ELSE rule enigne for logic operation
  • No more programming. Just click and get done!
  • Support IO, Counter, Timer, Email operations
  • Modbus/TCP Protocol for SCADA Software Seamless Integration
  • IEEE 802.3af-compliant Power over Ethernet (PoE)
  • 10/100 Base-TX Ethernet
  • AI Type: 7 RTD (Pt100, Pt1000, Ni120, Cu100, Cu1000)
  • Individual Channel Configuration
  • 3-wire RTD Input with Lead Resistance Elimination
  • 2-way Isolation/ESD Protection

Applications

Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.

Hardware Specifications

Analog Input
Input Channels 7 (Differential)
Sensor Type Pt100, Pt1000, Ni120, Cu100, Cu1000
Wire Connection 2/3 wire
Resolution 16-bit
Sampling Rate 12 Samples/Sec. (Total)
Accuracy ±0.05%
Zero Drift ±0.5 μV/°C
Span Drift ±20 μV/°C
Common Mode Rejection 150 dB
Normal Mode Rejection 100 dB
Input Impedance >1M Ω
Open Wire Detection Yes
Individual Channel Configurable Yes
3-wire RTD Lead Resistance Elimination Yes
System
CPU 16-bit CPU
SRAM 512 KB
Flash Memory 512 KB
EEPROM 16 KB
Watchdog Yes
Communication
PoE Ethernet Port 10/100 Base-TX and automatic MDI/MDI-X
2 Way Isolation
I/O 2500 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each terminal and ±8 kV Air for random point
EFT (IEC 61000-4-4) ±4 kV for Power Line 
LED Indicators
PoE PoE On
L1 System Running
L2 Ethernet Link/Act
L3 Ethernet 10/100M Speed
Power Requirements
Reserve Polarity Protection Yes
Powered from terminal block Yes, 12 ~ 48 VDC
Powered from PoE Yes, IEEE 802.3af, Class1
Consumption 2.6 W
Mechanical
Dimensions (W x H x D) 72 mm x 123 mm x 35 mm
Installation DIN-Rail or Wall mounting
Environment
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -30 °C ~ +80 °C
Humidity 10 ~ 90% RH, non-condensing

Software Specifications

Functions
Rule Configuration Website Access Web server on WISE controllers to edit and upload logic rules through web browser.
36 IF-THEN-ELSE Logic Rules 3 IF conditions with AND or OR operators
3 THEN actions and 3 ELSE actions
48 Internal Registers Hold temporary variables and read/write data via Modbus/TCP address.
12 Timers Delay / Timing functions.
12 Emails Send Email messages to pre-set Email receivers.
12 CGI Commands Send pre-set CGI commands.
12 Recipes Set up THEN/ELSE action groups.
8 P2P remote modules Set up the connection information for the remote WISE modules.
Modbus/TCP Protocol Real time control and monitoring I/O channels and system status of controllers via SCADA software.
IF Conditions
AI Channel = 、> 、< 、 ≥ 、 ≤ (value)
Internal Register
Timer Timeout、Not Timeout
P2P DI、AI、DI counter、DO counter、IR
Rule Status Enable、Disable
THEN / ELSE Actions
Internal Register Change the value
Timer Start、Stop
Email Send
CGI Commands
Recipe Execute
P2P DO(On/Off)、AO、IR
Rule Status Enable、Disable

Ordering Information

  • WISE-7115 CR
  • 7-channel RTD Input with 3-wire RTD lead resistance elimination PoE Module (RoHS)

Accessories

  • GPSU06U-6 : 24 V/0.25 A, 6 W Power Supply
  • MDR-20-24 : 24 V/1 A, 24 W Power Supply with DIN-Rail Mounting
  • NS-205 CR : Unmanaged 5-Port Industrial Ethernet Switch
  • NS-205PSE-24V CR : Unmanaged 5-Port Industrial PoE Ethernet Switch (RoHS)