WISE-7526M
![]() |
WISE I/O Module with 6-channels AI, 2-channels AO, 2-channels DI, 2-channels DO and 2-port Ethernet Switch | ||||
|
|
|||||
Introduction
WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the labor and cost spent on system development.
WISE-7526M is a multi-function module with 6-channel analog inputs, 2-channel analog outputs, 2-channel digital inputs and 2-channel digital outputs. It provides various programmable analog inputs, and analog outputs. Each analog input is allowed to configure a proper range with 240 Vrms high voltage protection. WISE-7526M follows IEEE 802.3af-compliant Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs. In additional to this, WISE-7526M also has a built-in two-port Ethernet switch to implement daisy-chain topology. The cabling is much easier and total costs of cable and switch are significantly reduced.
By integrating with IF-THEN-ELSE rule engine, WISE-7526M provides more powerful functions such as I/O Moniitoring/Control, Counter, Timer, Schedule, E-mail sending & CGI Command sending for use in various industrial applications. WISE-7526M also supports Modbus TCP and MQTT protocol to make seamless integration with SCADA, IT and IoT (Internet of Things) system.
Features
- Runs on browsers, no extra software tool is required.
- No more programming, Web pages provided for control logic editing.
- IF-THEN-ELSE logic rules execution ability.
- Built-in I/O (AI: 6 Channels; AO: 2 Channels; DI: 2 Channels; DO: 2 Channels)
- Support I/O Moniitoring/Control, Counter, Timer, Schedule, Email sending and CGI Command sending operations.
- Modbus TCP Protocol for SCADA System Integration.
- IEEE 802.3af-compliant Power over Ethernet (PoE).
- 2-port Ethernet Switch for Daisy-Chain Topology.
- MQTT Protocol for IT & IoT (Internet of Things) System Integration.
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.
Hardware Specifications
| Analog Input | ||
| Channels | 6 (Differential) | |
| Input Type | ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA, 0 to 20 mA, 4 to 20 mA (jumper selectable) |
|
| Resolution | 16-bit | |
| Sampling Rate | 10 Sample/Sec. (Total) | |
| Accuracy | ±0.1 % | |
| Zero Drift | ±20 μV/°C | |
| Span Drift | ±25 ppm/°C | |
| Overvoltage Protection | 240 Vrms | |
| Input Impedance | Voltage | 2 MΩ |
| Current | 125 Ω | |
| Common Mode Rejection | 86 dB Min. | |
| Normal Mode Rejection | 100 dB | |
| Individual Channel Configuration | Yes | |
| Analog Output | ||
| Channels | 2 | |
| Output Type | 0 to 5 VDC, ± 5 VDC, 0 to 10 VDC, ± 10 VDC, 0 to 20 mA, 4 to 20 mA (jumper selectable) |
|
| Individual Channel Configuration | Yes | |
| Resolution | 12-bit | |
| Accuracy | ± 0.1 % of FSR | |
| Voltage Output Capability | 20 mA @ 10 V | |
| Current Load Resistance | 500 Ω | |
| Open Wire Detection | Yes, for 4 to 20 mA only | |
| Digital Input | ||
| Channels | 2 | |
| Dry Contact (Source) |
On Voltage Level | Close to GND |
| Off Voltage Level | Open | |
| Effective Distance for Dry Contact | 500M Max. | |
| Wet contact (Sink/Source) |
On Voltage Level | +1 VDC Max. |
| Off Voltage Level | +3.5 VDC ~ +30 VDC | |
| Counters | Channels | 2 |
| Max. Counts | 16-bit (65535) | |
| Max. Input Frequency | 50 Hz | |
| Min. Pulse Width | 10 ms | |
| Overvoltage Protection | 30 VDC | |
| Digital Output | ||
| Channels | 2 | |
| Output Type | Isolated Open Collector (Sink) | |
| Max. Load Current | 700 mA/Channel | |
| Load Voltage | +5 VDC to +50 VDC | |
| Overvoltage Protection | 60 VDC | |
| Overload Protection | 1.4 A | |
| Short-circuit Protection | Yes | |
| Communication | ||
| Ethernet Port | 2 x RJ-45, 10/100 Base-TX, Swtich Ports | |
| PoE | Yes | |
| Protocol | Modbus TCP, MQTT | |
| LED Indicators | ||
| for System Running | Yes | |
| for Ethernet Link/Act | Yes | |
| for I/O Channel Status | Yes | |
| for PoE Power | Yes | |
| 2-Way Isolation | ||
| I/O | 2500 VDC | |
| EMS Protection | ||
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal and ±8 kV Air for Random Point |
|
| EFT (IEC 61000-4-4) | ±2 kV for Power Line | |
| Surge (IEC 61000-4-5) | ±2 kV for Power Line | |
| Power | ||
| Reverse Polarity Protection | Yes | |
| Powered from Terminal Block | 12 ~ 48 VDC | |
| Powered from PoE | Yes, IEEE 802.3af, Class1 | |
| Consumption | 4.4 W (Max.) | |
| Mechanical | ||
| Dimensions (L x W x H) | 120mm x 97mm x 42mm | |
| Installation | Wall mounting | |
| Environment | ||
| Operating Temperature | -25 °C to +75 °C | |
| Storage Temperature | -30 °C to +80 °C | |
| Humidity | 10 to 90% RH, non-condensing | |
Software Specifications
| Functions | |
| Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
| 72 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators 3 THEN actions and 3 ELSE actions |
| 48 Internal Registers | Hold temporary variables and read/write data |
| 24 Timers | Delay / Timing functions. |
| 24 Schedules | Setup prescheduled routine tasks. |
| 24 Emails | Send Email messages to pre-set Email receivers. |
| 24 CGI Commands | Send pre-set CGI commands. |
| 24 Recipes | Set up THEN/ELSE action groups. |
| 8 P2P remote modules | Set up the connection information for the remote WISE modules. |
| Modbus TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
| MQTT Protocol | Real time message publish/subscribe
mechanism for I/O channels and system status
via IT/IoT software. |
| IF Conditions | |
| DI Channel | ON, OFF, ON to OFF, OFF to ON, Change |
| AI Channel | = 、> 、< 、 ≥ 、 ≤ (value) |
| Internal Register | |
| DI Counter | = 、> 、< 、 ≥ 、 ≤ (value), Change |
| DO Counter | |
| Timer | Timeout, Not Timeout |
| Schedule | In Range, Out of Range |
| P2P | DI, AI, DI counter, DO counter, IR |
| Rule Status | Enable, Disable |
| THEN / ELSE Actions | |
| DO Channel | ON, OFF, Pulse Output |
| AO Channel | Change the value |
| Internal Register | |
| DI Counter | Reset |
| DO Counter | |
| Timer | Start, Reset |
| Schedule | Enable, Disable |
| Send | |
| MQTT message | |
| CGI Commands | |
| Recipe | Execute |
| P2P | DO(On/Off), AO, IR |
| Rule Status | Enable, Disable |
Ordering Information
- WISE-7526M CR
WISE IoT I/O Module with 6-channels AI, 2-channels AO, 2-channels DI, 2-channels DO and 2-port Ethernet Switch (RoHS)
Accessories
- GPSU06U-6 : 24 V/0.25 A, 6 W Power Supply
- MDR-20-24 : 24 V/1 A, 24 W Power Supply with DIN-Rail Mounting
- NS-205 CR : Unmanaged 5-Port Industrial Ethernet Switch (RoHS)
- NS-205PSE-24V CR : Unmanaged 5-Port Industrial PoE Ethernet Switch (RoHS)