WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the labor and cost spent on system development.
WISE-7555M provides 8 Dry/wet contact digital input channels and 8 source-type digital output channels. It features optical isolation for 2500 VDC of transient overvoltage protection but doesn’t provide channel-to-channel isolation. It can safely be used in applications where hazardous voltages are present. WISE-7555M follows IEEE 802.3af- compliant Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs. In additional to this, WISE-7555M also has a built-in two-port Ethernet switch to implement daisy-chain topology. The cabling is much easier and total costs of cable and switch are significantly reduced.
By integrating with IF-THEN-ELSE rule engine, WISE-7555M provides powerful functions such as I/O Monitoring/Control, Counter, Timer, Schedule, E-mail sending & CGI Command sending for use in various industrial applications. WISE-7555M also supports Modbus TCP and MQTT protocols to make seamless integration with SCADA, IT and IoT (Internet of Things) system.
Features
- Runs on browsers, no extra software tool is required.
- No more programming, Web pages provided for control logic editing.
- IF-THEN-ELSE logic rules execution ability.
- Built-in I/O (DI: 8 Channels; DO: 8 Channels)
- Support I/O Moniitoring/Control, Counter, Timer, Schedule, Email sending and CGI Command sending operations.
- Modbus TCP Protocol for SCADA System Integration.
- IEEE 802.3af-compliant Power over Ethernet (PoE).
- 2-port Ethernet Switch for Daisy-Chain Topology.
- MQTT Protocol for IT & IoT (Internet of Things) System Integration.
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.
Hardware Specifications
Digital Input/Counter | ||
Channels | 8 | |
Contact | Dry +Wet | |
Sink/Source (NPN/PNP) | Dry: Source Wet: Sink/Source |
|
Wet Contact | On Voltage Level | +10 VDC to +50 VDC |
Off Voltage Level | +4 VDC Max. | |
Dry Contact | On Voltage Level | Close to GND |
Off Voltage Level | Open | |
Input Impedance | 10 kΩ | |
Counters | Max. Counts | 16-bit (65535) |
Max. Input Frequency | 50 Hz | |
Min. Pulse Width | 10 ms | |
Overvoltage Protection | +70 VDC | |
Effective Distance | 500 M Max. | |
Digital Output | ||
Channels | 8 | |
Type | Isolated Open Collector | |
Sink/Source (NPN/PNP) | Source | |
Max. Load Current | 650 mA/channel at 25°C | |
Load Voltage | +10 VDC to +40 VDC | |
Overvoltage Protection | 47 VDC | |
Overload Protection | - | |
Short-circuit Protection | Yes | |
Communication | ||
Ethernet Port | 2 x RJ-45, 10/100 Base-TX, Swtich Ports | |
PoE | Yes | |
Protocol | Modbus TCP, MQTT | |
LED Indicators | ||
for System Running | Yes | |
for Ethernet Link/Act | Yes | |
for I/O Channel Status | Yes | |
for PoE Power | Yes | |
2-Way Isolation | ||
I/O | 2500 VDC | |
EMS Protection | ||
ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal and ±8 kV Air for Random Point |
|
EFT (IEC 61000-4-4) | ±2 kV for Power Line | |
Surge (IEC 61000-4-5) | ±2 kV for Power Line | |
Power | ||
Reverse Polarity Protection | Yes | |
Powered from Terminal Block | 12 to 48 VDC | |
Powered from PoE | Yes, IEEE 802.3af, Class1 | |
Consumption | 3.7 W (Max.) | |
Mechanical | ||
Dimensions (L x W x H) | 120mm x 97mm x 42mm | |
Installation | Wall mounting | |
Environment | ||
Operating Temperature | -25 °C to +75 °C | |
Storage Temperature | -30 °C to +80 °C | |
Humidity | 10 to 90% RH, non-condensing |
Software Specifications
Functions | |
Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
72 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators 3 THEN actions and 3 ELSE actions |
48 Internal Registers | Hold temporary variables and read/write data |
24 Timers | Delay / Timing functions. |
24 Schedules | Setup prescheduled routine tasks. |
24 Emails | Send Email messages to pre-set Email receivers. |
24 CGI Commands | Send pre-set CGI commands. |
24 Recipes | Set up THEN/ELSE action groups. |
8 P2P remote modules | Set up the connection information for the remote WISE modules. |
Modbus TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
MQTT Protocol | Real time message publish/subscribe
mechanism for I/O channels and system status
via IT/IoT software. |
IF Conditions | |
DI Channel | ON, OFF, ON to OFF, OFF to ON, Change |
Internal Register | = 、> 、< 、 ≥ 、 ≤ (value) |
DI Counter | = 、> 、< 、 ≥ 、 ≤ (value), Change |
DO Counter | |
Timer | Timeout, Not Timeout |
Schedule | In Range, Out of Range |
P2P | DI, AI, DI counter, DO counter, IR |
Rule Status | Enable, Disable |
THEN / ELSE Actions | |
DO Channel | ON, OFF, Pulse Output |
Internal Register | Change the value |
DI Counter | Reset |
DO Counter | |
Timer | Start, Reset |
Schedule | Enable, Disable |
Send | |
MQTT message | |
CGI Commands | |
Recipe | Execute |
P2P | DO(On/Off), AO, IR |
Rule Status | Enable, Disable |
Ordering Information
- WISE-7555M CR
WISE IoT I/O Module with 8-channels DI, 8-channels DO and 2-port Ethernet Switch. (RoHS)
Accessories
- GPSU06U-6 : 24 V/0.25 A, 6 W Power Supply
- MDR-20-24 : 24 V/1 A, 24 W Power Supply with DIN-Rail Mounting
- NS-205 CR : Unmanaged 5-Port Industrial Ethernet Switch (RoHS)
- NS-205PSE-24V CR : Unmanaged 5-Port Industrial PoE Ethernet Switch (RoHS)