WISE-7901 / WISE-7901D
WISE-7901 |
WISE-7901D |
User-defined I/O Expansion PoE Module | ||||
Introduction
WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development.
WISE-7901 follows IEEE 802.3af-compliant (classification, Class 1) Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs (Category 5 Ethernet cable). This feature provides greater flexibility and higher efficiency therefore simplifying systems design, saving space, reducing cables and eliminating the requirement for dedicated electrical outlets. Meanwhile, in case under a non-PoE environment, WISE-7901 will still be able to receive power from auxiliary power sources like AC adapters or battery, etc.
This module WISE-7901 supports Modbus/TCP protocol to make seamless integration with SCADA software available. It supports an I/O expansion bus to implement various I/O functions such as D/I, D/O, A/D, D/A according to the using X-Board.
Features
- Built-in Web Server for IF-THEN-ELSE rule setting
- Built-in IF-THEN-ELSE rule enigne for logic operation
- No more programming. Just click and get done!
- Support IO, Counter, Timer, Email operations
- Modbus/TCP Protocol for SCADA Software Seamless Integration
- IEEE 802.3af-compliant Power over Ethernet (PoE)
- 10/100 Base-TX Ethernet
- I/O expansion bus
- Support DI/DO X-Boards: X107, X109, X110, X111
- Support Multi-Function X-Boards: X202, X203, X303, X304, X305, X308, X310, X324
Applications
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.
Hardware Specifications
Model
|
WISE-7901
|
WISE-7901D
|
CPU Module | ||
CPU | 16-bit CPU | |
SRAM | 512 KB | |
Flash | 512 KB | |
EEPROM | 16 KB | |
NVRAM | 31 Bytes | |
OS | MiniOS7 | |
RTC (Real Time Clock) | RTC Provide seconds, minutes, hours, date of week/month; month and year, valid from 1980 to 2079 | |
64-bit Hardware Serial Number | Yes | |
Watchdog Timers | Yes (0.8 second) | |
Communication Ports | ||
Ethernet | RJ-45 x 1, 10/100 Base-TX (Auto-negotiating, Auto MDI/MDI-X, LED indicators) | |
COM 1 | No (Unsupported by WISE firmware) | |
COM 2 | No (Unsupported by WISE firmware) | |
LED Indicators | ||
System LED | Yes | |
LED Display | - | 5-digit 7-segment LED display |
Special Indicator | PoE LED | |
Hardware Expansion | ||
I/O Expansion Bus | Yes | |
Mechanical | ||
Dimensions (W x H x D) | 72 mm x 123 mm x 35 mm | |
Installation | DIN-Rail or Wall Mounting | |
Environment | ||
Operating Temperature | -25 ~ +75 °C | |
Storage Temperature | -40 ~ +80 °C | |
Ambient Relative Humidity | 5 ~ 90% RH, non-condensing | |
Power | ||
Protection | Power reverse polarity protection | |
Frame Ground | Yes (for ESD Protection) | |
Input Range | +12 ~ +48 VDC | |
Power over Ethernet (PoE) | IEEE 802.3af Class 1 | |
Power Consumption | 1.5 W | 2.5 W |
Software Specifications
Functions | |
Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
36 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators 3 THEN actions and 3 ELSE actions |
48 Internal Registers | Hold temporary variables and read/write data via Modbus/TCP address. |
12 Timers | Delay / Timing functions. |
12 Schedules | Setup prescheduled routine tasks. |
12 Emails | Send Email messages to pre-set Email receivers. |
12 CGI Commands | Send pre-set CGI commands. |
12 Recipes | Set up THEN/ELSE action groups. |
8 P2P remote modules | Set up the connection information for the remote WISE modules. |
Modbus/TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
IF Conditions | |
DI Channel | ON、OFF、ON to OFF、OFF to ON、Change |
AI Channel | = 、> 、< 、 ≥ 、 ≤ (value) |
Internal Register | |
DI Counter | = 、> 、< 、 ≥ 、 ≤ (value)、Change |
DO Counter | |
Timer | Timeout、Not Timeout |
Schedule | In Range、Out of Range |
P2P | DI、AI、DI counter、DO counter、IR |
Rule Status | Enable、Disable |
THEN / ELSE Actions | |
DO Channel | ON、OFF、Pulse Output |
AO Channel | Change the value |
Internal Register | |
DI Counter | Reset |
DO Counter | |
Timer | Start、Stop |
Schedule | |
Send | |
CGI Commands | |
Recipe | Execute |
P2P | DO(On/Off)、AO、IR |
Rule Status | Enable、Disable |
Ordering Information
- WISE-7901 CR
- WISE-7901D CR
User-defined I/O Expansion PoE Module (RoHS)
User-defined I/O Expansion PoE Module with LED Display (RoHS)
Accessories
- GPSU06U-6 : 24 V/0.25 A, 6 W Power Supply
- MDR-20-24 : 24 V/1 A, 24 W Power Supply with DIN-Rail Mounting
- NS-205 CR : Unmanaged 5-Port Industrial Ethernet Switch
- NS-205PSE-24V CR : Unmanaged 5-Port Industrial PoE Ethernet Switch (RoHS)
- I/O Expansion Boards : Other add-on expansion boards X107, X109, X110, X111, X202, X203, X303, X304, X305, X308, X310, X324